ViPIRS PANEL BASICS. FROM INSTALL TO USE
Follow these steps to install your ViPIRS infrared viewing panel. Find out everything you need to know here or call us for more information.

Getting started – safety first
- Ensure that the equipment you are working on is safety de-energised and locked-out, tagged-out prior to commencing installation.
- Always comply with local codes and best practices, wear appropriate personal protective equipment (PPE).
- The ViPIRS product line is Underwriters Laboratories (UL) approved for installation into electrical equipment in the vertical plane. Do not install into the horizontal plane.
Check your equipment
A ViPIRS Installation kit is available for V44BD units.
Installation of the ViPIRS infrared viewing panes is straightforward with the correct hand tools. We recommend:
- Electric drilling machine; if battery operated, with a spare battery and charger.
- Nibbler/grinder.
- 4.5mm diameter HSS metal drill bit.
- Centre punch.
- De-burring tool.
- PZ2 Pozi-drive screwdriver.
- Corrosion protection treatment.
Check what’s in the box
Verify your ViPIRS kit contains:
- ViPIRS infrared viewing pane.
- Installation instruction sheet.
- Fitting hardware (supplied attached to the ViPIRS).
Install the ViPIRS
- Mount the self-adhesive drilling template into position on the panel.
- Centre punch the holes indicated on the drilling template.
- Using the 4.5mm HSS bit, drill the fixing holes labelled on the drilling template.
- Cut the centre hole using your chosen tool. This guide assumes either a grinder, nibbler or a hydraulic punch tool will be used.
- Once the viewing hole is cut, de-burr the edges and apply corrosion protection treatment.
- Remove the remaining drilling template and discard responsibly.
- Align the body of the ViPIRS with the holes and fasten using the fixing hardware provided.
Your ViPIRS infrared viewing pane is installed and ready to provide years of trouble-free service.